VersiStart III LB Seeriad (9A~45A)
Features:
| |
Function:
Typical Applications:
|
Models:
Technical Data (standard)
|
VS III 480-9-LB
|
VS III 480-16-LB
| VS III 480-25-LB
|
VS III 480-37-LB
|
VS III 480-45-LB
| |
Reted device current
|
9A |
16A | 25A
| 37A
| 45A
| |
Motor rating at Ue 400V
|
4kW |
7,5kW |
11kW |
18,5kW |
22kW | |
Rated operation voltage Ue
|
200V-480V ± 10% 50/60Hz | |||||
Control supply voltage Us only with option B
|
230V ± 10% AC 50/60 Hz
| |||||
Max.switching frequency
at 2,5xIn and 5s tan at 2,5xIn and 1s tan |
10 40 |
6 24 |
4 16 |
3 12 |
2 8 | |
Max. power dissipation
- in operating related to max. starting frequency - standby |
9W 5W |
9W 5W |
9W 5W |
9W 5W |
9W 5W | |
I²t —power semiconductors in A²s | 390
| 720
| 4000
| 9100
| 16200
| |
Min. motor load | 20% of device rating
| |||||
Starting time
| 0,6s
| |||||
Stopping time
| 0,25s
| |||||
Restart time
| 200ms
| |||||
Input resistance control inputs
| 80kOhm
| |||||
Control voltage Uc | 24VDC … 230VAC | |||||
Contact rating of relay outputs RA1/RA2 | 2A / 250VAC / 30VDC | |||||
Installation class | 3
| |||||
Overvoltage category / pollution degree:
control and auxiliary circuit main circuit |
II / 2 III (TT / TN-systems) / 2 | |||||
Rated impulse strength Uimp:
control and auxiliary circuit main circuit |
2,5kV 4kV | |||||
Rated insulation voltage Ui:
control and auxiliary circuit main circuit |
250V 500V | |||||
Cross-sectional area for connection:
control terminals power terminals |
1,5mm² 6mm² |
1,5mm² 16mm² | ||||
Max tightening torque
control / power terminals main circuit |
- spring-loaded terminals - spring-loaded terminals | |||||
Ambient / storage temperature | 0°C ... 45°C up tp an altitude of 1000m / -25°C ... 75°C | |||||
Weight | 950g | |||||
Order number
| 2S511.48009 | 2S511.48016 | 2S511.48025 | 2S511.48037 | 2S511.48045 |
Dimensions:
Connection Diagram: