AC-MINISTART
![]() |
Features:
|
Functions:
*
- with standard devices closed, when power semiconductors are bridged
Typical Applications: |
![]() |
Models:
|
Technical Data |
MINISTART |
||||
|
1.5 |
3 |
5.5 |
7.5 |
11 |
|
|
Mains / Motor voltage according to DIN EN 50160 (IEC 38) |
400V ± 15% 50/60Hz |
||||
|
Device nominal current |
4A |
6.5A |
12A |
16A |
25A |
|
Motor rating |
1,5kW |
3kW |
5.5kW |
7.5kW |
11kW |
|
min. motor current |
10% of the device rated current |
||||
|
Starting torque |
0 … 80% |
||||
|
Acceleration time |
1 … 20s |
||||
|
Soft stop torque |
20 … 80% |
||||
|
Deceleration time |
0 … 20s |
||||
|
Reset time |
200ms |
||||
|
max. switching cycle at 3x Ie and 5s tan |
120/h |
60/h |
20/h |
||
|
Control terminals Power terminals |
1.5mm2 4.0mm2 |
||||
|
I2t-Value Power seniconductor |
40A2s |
450A2s |
550A2s |
9100A2s |
9100A2s |
|
Ambient / Storage temperature |
0ºC … 45ºC / -25ºC … 75ºC |
||||
|
Weight / kg |
1.2 |
1.2 |
1.35 |
1.5 |
1.5 |
|
Order number |
21200.38001 |
21200.38003 |
21200.38005 |
21200.38007 |
21200.38011 |
| Please observe supplementary sheet with dimensioning rules | |||||
Dimensions:

Connection Diagram: